Thomson Digital Energy Series - TS3

Certification and Standards: GB14048.11
- Rated current: 40A~630A (2, 3, and 4 poles)
- The neutral line has the same capacity as the phase line and is equipped with an independent arc extinguishing chamber
- Load usage category: AC-33A/AC-33B, Suitable for mixed loads
- Three levels, the middle position can effectively and safely isolate, ensuring safe operation (optional)
- DC coil drive mechanism, conversion action time<100ms
- Built in mechanical and electrical interlocking functions
- Multiple working modes: manual/automatic/automatic switching and recovery/mutual backup
- Adjustable delay parameter on site from 0 to 999s
- Displayed line voltage values and delay parameters
- Parameter modification password protection function
- Power status and switch position indicated by LED
- Nearly 100 searchable event records
- Equipped with RS485 communication function, convenient for integration of backend monitoring system
- Equipped with dry contact for starting the generator